Understanding Cooling and Heating Loads
Contents |
[edit] Introduction
As a knowledgeable professional in the HVAC industry, it’s crucial to provide accurate advice to designers, not only to improve your own credibility but also to enhance their projects and potentially secure more orders. To facilitate this process, we have compiled a set of rules of thumb that can be applied to most general applications. However, it’s imperative to emphasise that while we are well-versed in HVAC principles, we are not designers, and our advice should always be verified by others before installation. This disclaimer must be clearly stated in all written communications if our equipment design is based on these rules of thumb.
[edit] Cooling Loads
When considering cooling loads, a general guideline is to allocate 120 – 160 watts per square meter, taking into account factors such as solar gain, people, and lighting. Alternatively, you can estimate the cooling requirement at 1 kilowatt per occupant. Additionally, for each meter per second of fresh air introduced, add approximately 10 kilowatts to the total cooling load. If a designer provides the desired cooling load in kilowatts, a quick crosscheck can be performed using the rule of thumb that suggests a maximum of 20 kilowatts per cubic meter of air. Any value surpassing this threshold will likely necessitate an increase in air volume.
To calculate the cooling load using psychometric charts, the following equation can be applied: Cooling Load (kW) = Enthalpy Difference (total heat content) x Air Volume Specific Volume (m³/kg) at the entering condition
For example, consider the following data: Air Volume: 1.5 m³/s Entering Air Temperature (EAT): 28°C dry bulb / 50% relative humidity (Specific Enthalpy: 59 kJ/kg) Leaving Air Temperature (LAT): 12°C dry bulb / 11.5°C wet bulb (Specific Enthalpy: 33 kJ/kg)
Using the equation, the calculation would be as follows: Cooling Load (kW) = (59 – 33) x 1.5 m³/s / 0.869 m³/kg Therefore, the cooling load amounts to 44.88 kW.
[edit] Heating Loads
For heating loads, a general rule of thumb suggests allocating 45 watts per cubic meter, considering the volume of the space. Additionally, when accounting for fresh air load, a standard equation can be used: kW = AT°C × 1.207 (constant) × M.
It’s important to note that this guideline is applicable when heating the building using the Air Handling Unit (AHU). In cases where heating is provided through alternative means, such as radiators, the equation kW = OT°C × 1.207 × M should be employed for tempered ventilation.
[edit] Conclusion
By utilising these rules of thumb, HVAC professionals can assist designers in estimating cooling and heating loads for various applications. However, it is crucial to emphasise that these guidelines serve as initial estimations and should be verified by qualified designers to ensure accuracy and compliance with specific project requirements. Clear communication about our role, lack of design liability insurance, and the need for independent design verification should be included in all written correspondences. By adhering to these principles, we can enhance our credibility, improve collaboration with designers, and deliver superior HVAC solutions.
--Building Ventilation Solutions
[edit] Related articles on Designing Buildings
- Air conditioning.
- Air handling unit.
- Approved Document F.
- Building services
- Building services engineer.
- Condensation.
- Dehumidification.
- Displacement ventilation.
- Ductwork.
- Dehumidification.
- Dry-bulb temperature.
- Fan coil unit.
- Heating.
- Humidification.
- HVACR.
- Humidification.
- Humidistat.
- HVAC.
- Interstitial condensation.
- Mechanical, electrical and plumbing MEP.
- Mechanical ventilation.
- Moisture content.
- Natural ventilation.
- Plant room.
- Psychometric chart.
- Refrigeration.
- Sling psychrometer.
- Thermal comfort.
- Thermal indices.
- Ventilation.
- Water vapour.
- Wet-bulb temperature.
[edit] External links
Other articles by author Simon Windsor https://www.bvs-ltd.co.uk/author/simon/
Featured articles and news
About the 5 Percent Club and its members
The 5% Club; a dynamic movement of employers committed to building and developing the workforce.
New Homes in New Ways at the Building Centre
Accelerating the supply of new homes with MMC.
Quality Planning for Micro and Small to Medium Sized Enterprises
A CIOB Academy Technical Information sheet.
A briefing on fall protection systems for designers
A legal requirement and an ethical must.
CIOB Ireland launches manifesto for 2024 General Election
A vision for a sustainable, high-quality built environment that benefits all members of society.
Local leaders gain new powers to support local high streets
High Street Rental Auctions to be introduced from December.
Infrastructure sector posts second gain for October
With a boost for housebuilder and commercial developer contract awards.
Sustainable construction design teams survey
Shaping the Future of Sustainable Design: Your Voice Matters.
COP29; impacts of construction and updates
Amid criticism, open letters and calls for reform.
The properties of conservation rooflights
Things to consider when choosing the right product.
Adapting to meet changing needs.
London Build: A festival of construction
Co-located with the London Build Fire & Security Expo.
Tasked with locating groups of 10,000 homes with opportunity.
Delivering radical reform in the UK energy market
What are the benefits, barriers and underlying principles.
Information Management Initiative IMI
Building sector-transforming capabilities in emerging technologies.
Recent study of UK households reveals chilling home truths
Poor insulation, EPC knowledge and lack of understanding as to what retrofit might offer.
Comments
[edit] To make a comment about this article, click 'Add a comment' above. Separate your comments from any existing comments by inserting a horizontal line.
Thanks for a useful article. Did you know you can set up a profile for your company, with details, logo and website. If you associate the article to that profile, then the company profile will appear at the top of the article.
Other forms of marketing within an article will normally be deleted. Find out more on this page https://www.designingbuildings.co.uk/wiki/Create_a_new_article